Honeywell V8043F1036 Replacement Part
Note: Use this valve in closed loop hydronic systems that do not contain dissolved oxygen in system water, such as fresh water from frequent source of makeup water. Valve designed for cycling (not constantly powered on) applications.
Includes:
- (1) - Motorized Zone Valve (V8043F1036)
- (1) - Installation Instructions (95-6983-12)
Specifications
- Manufacturer: Honeywell
- Model # V8043F1036
- Voltage: 24 VAC
- Amps: 0.32
- Power Consumption: 7.7 VA
- timing: Nominal Open 15 Seconds
- Ambient Temperature Range: 125°F (52°C)
- Connection Type: Sweat
- Body Pattern: 2-Way, Straight Through
- Pipe Size: 3/4"
- Fluid Temperature Range: 50°F to 200°F (10°C to 93°C)
- Maximum Differential Pressure Rating: 20 psi (138 kPa)
- Electrical Connections: Screw Terminals
- Valve Action: Spring Return to Close
- Body Material: Brass
- Stem Material: Stainless Steel
- End Switch Rating: 50 VA Pilot Duty @ 24 V' 4.4 Amps running with 26.4 Amps Inrush @ 120 VAC
- Actuation: 2 Position
- De-Energized Position: Normally Closed
- Auxiliary End Switch: Normally Open, Single-Pole, Single Throw
- Static Pressure Rating: 125 psi (862 kPa)
Replaces Old Honeywell Part Numbers
- There are no older part numbers.
Other Part Numbers
Honeywell, Zone Valve, V8043F1036, Tradeline, V8043 F 1036, Motorized Valve, 40004370-035
Fits Models:
(Press ctrl + F to find model number below.)
Replacement for Honeywell (V2031A, V2031B, V3048A1029, V8043B1027, V8043E1012, V8043F1010), Detroit (ZV200, ZV210), White-Rodgers (1361-102, 13A01-102, 13A02-102), Taco (556, 557, 571, 548A), Flair (VJ1C2, VJ2C2, V2ACA, VJ1B2, VJ1E2, VJ2D2), J-Evans (551, 552, 553, J2, J4), Erie (635B8-18A-8, 635B307-18A1, 635B307-18A0, 601, 607, 612, 621, 627, 647), Bell & Gossett (TEV 3/4, M1)